Description

Applications:  Wiring of Communication, Electronic Equipment and Switchboards

Conductor:  Tinned Copper Wire (TCW) to AS/NZS 1125

Insulation:  RoHS Compliant V90HT (105) P.V.C. to AS/NZS 3808

Colours: Black, Blue, Brown, Green / Yellow, Grey, Orange, Pink, Red, Violet, White, Yellow

Packs:100, 500, 1000 metres – other packs by request

  • Conductor No: Dia(mm)  16/0.20
  • Nominal Area (mm²:  0.5
  • Insulation Thickness (mm): 0.8
  • AMP Rating:  10
  • Electrical Resistance at 20°C (ohm/km):  40.1
  • Nominal O.D. (mm):  2.6
  • Mass (kg/100m): 1.1

Where used as Fixed Wiring, AMP ratings to AS/NZS 3008.1.1:2009 Table 4 Unenclosed-Spaced 40°C (in air), 25°C (in ground). Refer AS/NZS 3008 for derating factors.
Maximum operating temperature: 75°C in normal use OR 105°C where not subject to, or is protected from, mechanical damage (refer AS/NZS 3008.1.1:2009 Table 1 Clause 3).